The fault name
Three Phases Are Under voltage
Fault code
107
Number of flashing red lights
2
Troubleshooting and illustration
1.When the voltage between L1 and N, L2 and N, and L3 and N are all lower than 190V, the fault is reported.
2.Check the voltage between L1 and N, L2 and N, and L3 and N.
3.Measure the voltage between input L1 and N, L2 and N, L3 and N is about 230V this fault is eliminated.
The fault name
Phase L1 Undervoltage
Fault code
106
Number of flashing red lights
2
Troubleshooting and illustration
1.Check the voltage between the AC input line L1 and N.
2.When the voltage between L1 and N is lower than 190V, the fault is reported.
3.Measurement input voltage L1 and N value is about 230V this fault is eliminated.
The fault name
phase L1 over voltage
Fault code
105
Number of flashing red lights
1
Troubleshooting and illustration
1.Check the voltage between the AC input line L1 and N.
2.When the voltage between L1 and N exceeds 264V, the fault is reported.
3.Measurement input voltage L1 and N value is about 230V this fault is eliminated.
The fault name
Phase L3 Undervoltage
Fault code
104
Number of flashing red lights
2
Troubleshooting and illustration
1.Check the voltage between the AC input line L2 and N.
2.When the voltage between L2 and N is lower than 190V, the fault is reported.
3.Measurement input voltage L2 and N value is about 230V this fault is eliminated.
The fault name
Phase L3 Undervoltage
Fault code
103
Number of flashing red lights
1
Troubleshooting and illustration
1.Check the voltage between the AC input line L2 and N.
2.When the voltage between L2 and N exceeds 264V, the fault is reported.
3.Measurement input voltage L2 and N value is about 230V this fault is eliminated.
The fault name
Emergency stop press or emergency stop is broken
Fault code
100
Number of flashing red lights
3
Troubleshooting and illustration
1、Find this red button on the side of the charging pile.
2、The emergency stop fault is removed by clockwise rotation.
The fault name
Phase L3 Undervoltage
Fault code
102
Number of flashing red lights
2
Troubleshooting and illustration
1.Check the voltage between the AC input line L3 and N.
2.When the voltage between L3 and N is lower than 190V, the fault is reported.
3.Measurement input voltage L3 and N value is about 230V this fault is eliminated.
The fault name
phase L3 overvoltage
Fault code
101
Number of flashing red lights
1
Troubleshooting and illustration
1.Check the voltage between the AC input line L3 and N.
2.When the voltage between L3 and N exceeds 264V, the fault is reported.
3.Measurement input voltage L3 and N value is about 230V this fault is eliminated.